{"id":3779,"date":"2026-10-07T20:11:47","date_gmt":"2026-10-07T18:11:47","guid":{"rendered":"https:\/\/solid-safety.de\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/"},"modified":"2026-10-12T17:56:00","modified_gmt":"2026-10-12T15:56:00","slug":"fire-watch-fire-alarm-off-data-hall","status":"publish","type":"post","link":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/","title":{"rendered":"Fire Watch When the Fire Alarm Is Off: What General Contractors Should Know During Data Hall Fit-Out"},"content":{"rendered":"<p>During data hall fit-out, the fire alarm control panel is often switched off for the affected area \u2013 because works create dust, detectors are not yet finally installed or false alarms need to be avoided. During this period automatic fire detection is missing. A fire watch closes that gap.<\/p>\n<h2>When is a fire watch needed?<\/h2>\n<p>Whenever automatic fire detection is out of service in an area where work is going on or materials are stored. Whether and to what extent a fire watch is required follows from the fire protection concept, the operator&#8217;s requirements and, where applicable, the insurer. Agree this early with the fire safety officer.<\/p>\n<h2>What a fire watch must deliver<\/h2>\n<p><strong>Continuous presence<\/strong> in the affected area while the fire alarm is off.<br \/><strong>Extinguishers within reach<\/strong> \u2013 suitable extinguishers right in the work area.<br \/><strong>Regular patrols<\/strong> through all affected rooms.<br \/><strong>Clear escalation paths<\/strong> to the fire brigade and site management.<br \/><strong>Complete records<\/strong> of the start and end of the shutdown, patrols and incidents.<\/p>\n<h2>Typical mistakes<\/h2>\n<p>Fire watch staff taking on other tasks on the side, missing handovers between shifts, unclear responsibility for switching the system back on, and missing documentation. On large sites with several data halls a fixed procedure pays off.<\/p>\n<h2>Qualification<\/h2>\n<p>Fire watch staff should be trained fire safety assistants, know the site and be able to provide first aid. Full PPE is mandatory on data center sites.<\/p>\n<h2>Fire watch from Solid Safety<\/h2>\n<p>Solid Safety provides fire watch for data center construction sites across Germany \u2013 trained fire safety assistants and first aiders, documented in our digital logbook and connected to our 24-hour control room. More at <a href=\"https:\/\/solid-safety.de\/fire-watch\/?lang=en\">Fire watch<\/a>.<\/p>\n<p><strong>Fire alarm going offline?<\/strong> <a href=\"https:\/\/solid-safety.de\/contact\/?lang=en\">Request fire watch &rarr;<\/a><\/p>\n<div class=\"ss-post-author\">\n<div><strong>Sharif Jusufi<\/strong> \u2013 Managing Director of Solid Safety.<\/div>\n<\/div>\n<p class=\"ss-post-back\"><a href=\"https:\/\/solid-safety.de\/en\/insights\/?lang=en\">\u2190 All insights<\/a><\/p>\n","protected":false},"excerpt":{"rendered":"<p>Why a fire watch is needed during data hall fit-out when the fire alarm control panel is switched off \u2013 and what matters in practice.<\/p>\n","protected":false},"author":1,"featured_media":4542,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"inline_featured_image":false,"_jetpack_newsletter_access":"","_jetpack_dont_email_post_to_subs":false,"_jetpack_newsletter_tier_id":0,"_jetpack_memberships_contains_paywalled_content":false,"_jetpack_feature_clip_id":0,"_jetpack_memberships_contains_paid_content":false,"footnotes":"","jetpack_post_was_ever_published":false},"categories":[64],"tags":[],"class_list":["post-3779","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-fire-safety"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.6 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Fire Watch When the Fire Alarm Is Off | Solid Safety<\/title>\n<meta name=\"description\" content=\"Why a fire watch is needed during data hall fit-out when the fire alarm control panel is switched off \u2013 tasks, qualifications and typical mistakes.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Fire Watch When the Fire Alarm Is Off | Solid Safety\" \/>\n<meta property=\"og:description\" content=\"Why a fire watch is needed during data hall fit-out when the fire alarm control panel is switched off \u2013 tasks, qualifications and typical mistakes.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/\" \/>\n<meta property=\"og:site_name\" content=\"Solid Safety\" \/>\n<meta property=\"article:published_time\" content=\"2026-10-07T18:11:47+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-10-12T15:56:00+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/blog-brandwache-rechenzentrum.webp\" \/>\n\t<meta property=\"og:image:width\" content=\"1600\" \/>\n\t<meta property=\"og:image:height\" content=\"893\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/webp\" \/>\n<meta name=\"author\" content=\"Sharif Jusufi\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Sharif Jusufi\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/\"},\"author\":{\"name\":\"Sharif Jusufi\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#\\\/schema\\\/person\\\/87c099c4b480a6bc3df6c3ff53f40195\"},\"headline\":\"Fire Watch When the Fire Alarm Is Off: What General Contractors Should Know During Data Hall Fit-Out\",\"datePublished\":\"2026-10-07T18:11:47+00:00\",\"dateModified\":\"2026-10-12T15:56:00+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/\"},\"wordCount\":305,\"publisher\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#organization\"},\"image\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/solid-safety.de\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/blog-brandwache-rechenzentrum.webp\",\"articleSection\":[\"Fire safety\"],\"inLanguage\":\"en-US\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/\",\"url\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/\",\"name\":\"Fire Watch When the Fire Alarm Is Off | Solid Safety\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/solid-safety.de\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/blog-brandwache-rechenzentrum.webp\",\"datePublished\":\"2026-10-07T18:11:47+00:00\",\"dateModified\":\"2026-10-12T15:56:00+00:00\",\"description\":\"Why a fire watch is needed during data hall fit-out when the fire alarm control panel is switched off \u2013 tasks, qualifications and typical mistakes.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/#primaryimage\",\"url\":\"https:\\\/\\\/solid-safety.de\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/blog-brandwache-rechenzentrum.webp\",\"contentUrl\":\"https:\\\/\\\/solid-safety.de\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/blog-brandwache-rechenzentrum.webp\",\"width\":1600,\"height\":893,\"caption\":\"Brandwache mit Feuerl\u00f6scher bei Hei\u00dfarbeiten in einer Data Hall im Ausbau (KI-generiert)\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/2026\\\/10\\\/07\\\/fire-watch-fire-alarm-off-data-hall\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Fire Watch When the Fire Alarm Is Off: What General Contractors Should Know During Data Hall Fit-Out\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#website\",\"url\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/\",\"name\":\"Solid Safety\",\"description\":\"Sicherheitsdienst und Site Support f\u00fcr kritische Infrastruktur \u2013 Rechenzentren, Baustellen, Objekte und Logistikzentren\",\"publisher\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#organization\",\"name\":\"Solid Safety\",\"alternateName\":\"Solid Safety GmbH\",\"url\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/solid-safety.de\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/logo-kopf-scaled.png\",\"contentUrl\":\"https:\\\/\\\/solid-safety.de\\\/wp-content\\\/uploads\\\/2026\\\/10\\\/logo-kopf-scaled.png\",\"width\":2560,\"height\":980,\"caption\":\"Solid Safety\"},\"image\":{\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#\\\/schema\\\/logo\\\/image\\\/\"},\"sameAs\":[\"https:\\\/\\\/www.linkedin.com\\\/company\\\/solid-safety-gmbh\\\/\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/solid-safety.de\\\/en\\\/#\\\/schema\\\/person\\\/87c099c4b480a6bc3df6c3ff53f40195\",\"name\":\"Sharif Jusufi\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/8cf733a75bfecf8026cdd8d2454070e9179c5e77640057334cc71cf0ff02a2f8?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/8cf733a75bfecf8026cdd8d2454070e9179c5e77640057334cc71cf0ff02a2f8?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/8cf733a75bfecf8026cdd8d2454070e9179c5e77640057334cc71cf0ff02a2f8?s=96&d=mm&r=g\",\"caption\":\"Sharif Jusufi\"},\"sameAs\":[\"https:\\\/\\\/solid-safety.de\"]}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Fire Watch When the Fire Alarm Is Off | Solid Safety","description":"Why a fire watch is needed during data hall fit-out when the fire alarm control panel is switched off \u2013 tasks, qualifications and typical mistakes.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/","og_locale":"en_US","og_type":"article","og_title":"Fire Watch When the Fire Alarm Is Off | Solid Safety","og_description":"Why a fire watch is needed during data hall fit-out when the fire alarm control panel is switched off \u2013 tasks, qualifications and typical mistakes.","og_url":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/","og_site_name":"Solid Safety","article_published_time":"2026-10-07T18:11:47+00:00","article_modified_time":"2026-10-12T15:56:00+00:00","og_image":[{"width":1600,"height":893,"url":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/blog-brandwache-rechenzentrum.webp","type":"image\/webp"}],"author":"Sharif Jusufi","twitter_card":"summary_large_image","twitter_misc":{"Written by":"Sharif Jusufi","Est. reading time":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/#article","isPartOf":{"@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/"},"author":{"name":"Sharif Jusufi","@id":"https:\/\/solid-safety.de\/en\/#\/schema\/person\/87c099c4b480a6bc3df6c3ff53f40195"},"headline":"Fire Watch When the Fire Alarm Is Off: What General Contractors Should Know During Data Hall Fit-Out","datePublished":"2026-10-07T18:11:47+00:00","dateModified":"2026-10-12T15:56:00+00:00","mainEntityOfPage":{"@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/"},"wordCount":305,"publisher":{"@id":"https:\/\/solid-safety.de\/en\/#organization"},"image":{"@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/#primaryimage"},"thumbnailUrl":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/blog-brandwache-rechenzentrum.webp","articleSection":["Fire safety"],"inLanguage":"en-US"},{"@type":"WebPage","@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/","url":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/","name":"Fire Watch When the Fire Alarm Is Off | Solid Safety","isPartOf":{"@id":"https:\/\/solid-safety.de\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/#primaryimage"},"image":{"@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/#primaryimage"},"thumbnailUrl":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/blog-brandwache-rechenzentrum.webp","datePublished":"2026-10-07T18:11:47+00:00","dateModified":"2026-10-12T15:56:00+00:00","description":"Why a fire watch is needed during data hall fit-out when the fire alarm control panel is switched off \u2013 tasks, qualifications and typical mistakes.","breadcrumb":{"@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/#primaryimage","url":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/blog-brandwache-rechenzentrum.webp","contentUrl":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/blog-brandwache-rechenzentrum.webp","width":1600,"height":893,"caption":"Brandwache mit Feuerl\u00f6scher bei Hei\u00dfarbeiten in einer Data Hall im Ausbau (KI-generiert)"},{"@type":"BreadcrumbList","@id":"https:\/\/solid-safety.de\/en\/2026\/10\/07\/fire-watch-fire-alarm-off-data-hall\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/solid-safety.de\/en\/"},{"@type":"ListItem","position":2,"name":"Fire Watch When the Fire Alarm Is Off: What General Contractors Should Know During Data Hall Fit-Out"}]},{"@type":"WebSite","@id":"https:\/\/solid-safety.de\/en\/#website","url":"https:\/\/solid-safety.de\/en\/","name":"Solid Safety","description":"Sicherheitsdienst und Site Support f\u00fcr kritische Infrastruktur \u2013 Rechenzentren, Baustellen, Objekte und Logistikzentren","publisher":{"@id":"https:\/\/solid-safety.de\/en\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/solid-safety.de\/en\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/solid-safety.de\/en\/#organization","name":"Solid Safety","alternateName":"Solid Safety GmbH","url":"https:\/\/solid-safety.de\/en\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/solid-safety.de\/en\/#\/schema\/logo\/image\/","url":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/logo-kopf-scaled.png","contentUrl":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/logo-kopf-scaled.png","width":2560,"height":980,"caption":"Solid Safety"},"image":{"@id":"https:\/\/solid-safety.de\/en\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/www.linkedin.com\/company\/solid-safety-gmbh\/"]},{"@type":"Person","@id":"https:\/\/solid-safety.de\/en\/#\/schema\/person\/87c099c4b480a6bc3df6c3ff53f40195","name":"Sharif Jusufi","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/secure.gravatar.com\/avatar\/8cf733a75bfecf8026cdd8d2454070e9179c5e77640057334cc71cf0ff02a2f8?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/8cf733a75bfecf8026cdd8d2454070e9179c5e77640057334cc71cf0ff02a2f8?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/8cf733a75bfecf8026cdd8d2454070e9179c5e77640057334cc71cf0ff02a2f8?s=96&d=mm&r=g","caption":"Sharif Jusufi"},"sameAs":["https:\/\/solid-safety.de"]}]}},"jetpack_sharing_enabled":true,"jetpack_featured_media_url":"https:\/\/solid-safety.de\/wp-content\/uploads\/2026\/10\/blog-brandwache-rechenzentrum.webp","_links":{"self":[{"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/posts\/3779","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/comments?post=3779"}],"version-history":[{"count":5,"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/posts\/3779\/revisions"}],"predecessor-version":[{"id":4695,"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/posts\/3779\/revisions\/4695"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/media\/4542"}],"wp:attachment":[{"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/media?parent=3779"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/categories?post=3779"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/solid-safety.de\/en\/wp-json\/wp\/v2\/tags?post=3779"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}